XTCuZ1-K PLUS (AS+) Marine cable 5 x 2.5mm² (LSZH) (0.6/1kV)

Technical data

Conductor type

Copper, class 5 (flexible)

Halogen-free

Flame resistant

UV-resistant

Yes

Color

Description

The XTCuZ1-K (AS+) halogen-free fireproof marine cable 0.6/1 kV is specially designed for installations where electrical power supply must remain guaranteed during a fire. This cable ensures the operation of essential emergency circuits such as signal lights, smoke extraction systems, acoustic alarms, water pumps and other critical safety installations even under extreme conditions.

In case of fire, the cable does not emit toxic or corrosive gases and produces very little smoke, ensuring both the safety of persons and the protection of sensitive electronic equipment. Thanks to these properties, this cable is particularly suitable for marine applications.

Key features:

  • Flexible copper conductor, class 5
  • Mica tape + HF XLPE conductor insulation (90 °C) for fire resistance
  • Aluminum polyester screen with overlapping tinned copper braid for 100% shielding
  • Halogen-free, fire-resistant outer jacket
  • Rated voltage: 0.6/1 kV
  • Maximum conductor temperature: 90 °C
  • Maximum short-circuit temperature: 250 °C (max. 5 s)
  • Minimum operating temperature: -40 °C (fixed and protected installation)
  • Fire-resistant for a minimum of 90 minutes at 840 °C
  • Flame retardant and non-flammable
  • Low smoke generation (light transmission > 60%)
  • Halogen-free and low corrosive gas emission
  • Distinctive orange outer jacket for safety identification
  • Fully shielded construction for optimum EMC protection

Mechanical and environmental resistance:

  • Mechanical load: AG3 (high load)
  • Good chemical and oil resistance
  • UV-resistant according to EN 50618
  • Water resistance: AD6
  • Minimum bending radius: 6x cable diameter

Installation conditions:

  • Outdoors
  • In tube at gunpoint
  • At gunpoint

Typical applications:

  • Emergency and safety circuits on board ships
  • Offshore installations and platforms
  • Engine rooms and technical rooms
  • Smoke extraction and fire detection systems on board
  • Power supply circuits for critical maritime infrastructure
  • EMC-sensitive installations where shielding is required

Note

The listed product information and technical data are compiled with the utmost care but may differ from reality. Images, specifications, and descriptions are indicative and non-binding.

TOP