H07ZZ-F Rubber cable 1 x 500mm² (LSZH) (450/750V)

Technical data

Conductor type

Copper, class 5 (flexible)

Voltage
CPR class

B2ca-s1b,d1,a1, Cca-s1b,d2,a1

Halogen-free

Yes

Flame-retardant

Yes

UV-resistant

No

Color

Black

Tags: ,

Description

The H07ZZ-F is a halogen-free, flexible rubber cable specifically used in mobile installations where low smoke and halogen-free fumes are required under fire conditions. This cable is suitable for applications with medium mechanical loads mainly in industrial and agricultural environments.

Thanks to its flexible copper conductor (class 5), halogen-free thermosetting rubber insulation (EI8) and CPR fire class B2ca-s1b,d1,a1 or Cca-s1b,d2,a1 (depending on cable section), this cable is suitable for machines in workshops, motors, transportable machines on construction sites, windmills and agricultural applications.

Key features:

  • Flexible copper conductor (class 5)
  • Halogen-free thermoset rubber insulation (EI8)
  • Halogen-free thermoset rubber outer jacket (EM8)
  • Rated voltage: 450/750 V
  • Maximum conductor temperature: 90°C
  • Maximum short-circuit temperature: 250°C (max. 5 s)
  • Minimum operating temperature: -40°C
  • CPR response to fire: B2ca-s1b,d1,a1 or Cca-s1b,d2,a1 (depending on cable section)
  • Flame retardant according to EN 60332-1 / IEC 60332-1
  • Non-flammable according to EN 60332-3-24 / IEC 60332-3-24 and EN 50399
  • Excellent oil, grease and chemical resistance
  • Water resistance: AD7
  • Mechanical load: AG2
  • Minimum bending radius:
    • 3x cable diameter (< 12 mm)
    • 4x cable diameter (≥ 12 mm)

Installation options:

  • Outdoors
  • In tube

Typical applications:

  • Machinery in industrial workshops
  • Agricultural workshops and installations
  • Motors
  • Transportable machines on construction sites
  • Windmills
  • Mobile power supplies

Note

The listed product information and technical data are compiled with the utmost care but may differ from reality. Images, specifications, and descriptions are indicative and non-binding.

TOP